Code Description
1502 AO1 CONTENT MIN
Sets the minimum
content value.
• Content is the
parameter
selected by
parameter 1501.
• Minimum value
refers to the
minimum content
value that will be
converted to an
analogue output.
• These
parameters
(content and
current min. and
max. settings)
provide scale
and offset
adjustment for
the output. See
the figure.
1503 AO1 CONTENT MAX
Sets the maximum content value
• Content is the parameter selected by parameter 1501.
• Maximum value refers to the maximum content value that will be
converted to an analogue output.
1504 MINIMUM AO1
Sets the minimum output current.
1505 MAXIMUM AO1
Sets the maximum output current.
1506 FILTER AO1
Defines the filter time constant for
• The filtered signal reaches 63% of a step change within the time
specified.
• See the figure for parameter 1303.
1507 AO2 CONTENT SEL
Defines the content for analogue output
above.
1508 AO2 CONTENT MIN
Sets the minimum content value. See
Parameter listing and descriptions
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
AO (mA)
P 1505 /
P 1511
P 1504 /
P 1510
P 1502/1508
AO (mA)
P 1505 /
P 1511
P 1504 /
P 1510
P 1503/1509
1.
AO
AO
1
AO
CONTENT MIN
Range
-
AO CONTENT
P 1503/1509
AO CONTENT
P 1502/1508
-
0.0...20.0 mA
0.0...20.0 mA
0.0...10.0 s
99...178
2. See
1
AO
CONTENT SEL
-
above.
207