Code Description
3704 LOAD FREQ 1
Defines the frequency value of the first load curve definition point.
• Must be smaller than 3707
3705 LOAD TORQ LOW 1
Defines the torque value of the first underload curve definition point.
• Must be smaller than 3706
3706 LOAD TORQ HIGH 1
Defines the torque value of the first overload curve definition point.
3707 LOAD FREQ 2
Defines the frequency value of the second load curve definition point.
• Must be smaller than 3710
3708 LOAD TORQ LOW 2
Defines the torque value of the second underload curve definition point.
• Must be smaller than 3709
3709 LOAD TORQ HIGH 2
Defines the torque value of the second overload curve definition point.
3710 LOAD FREQ 3
Defines the frequency value of the third load curve definition point.
• Must be smaller than 3713
3711 LOAD TORQ LOW 3
Defines the torque value of the third underload curve definition point.
• Must be smaller than 3712
3712 LOAD TORQ HIGH 3
Defines the torque value of the third overload curve definition point.
3713 LOAD FREQ 4
Defines the frequency value of the fourth load curve definition point.
• Must be smaller than 3716
3714 LOAD TORQ LOW 4
Defines the torque value of the fourth underload curve definition point.
• Must be smaller than 3715
3715 LOAD TORQ HIGH 4
Defines the torque value of the fourth overload curve definition point.
3716 LOAD FREQ 5
Defines the frequency value of the fifth load curve definition point.
3717 LOAD TORQ LOW 5
Defines the torque value of the fifth underload curve definition point.
• Must be smaller than 3718
3718 LOAD TORQ HIGH 5
Defines the torque value of the fifth overload curve definition point.
Parameter listing and descriptions
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Range
0...500 Hz
2.
LOAD FREQ
0...600%
1
LOAD TORQ HIGH
0...600%
0...500 Hz
3.
LOAD FREQ
0...600%
2.
LOAD TORQ HIGH
0...600%
0...500 Hz
4.
LOAD FREQ
0...600%
3.
LOAD TORQ HIGH
0...600%
0...500 Hz
5.
LOAD FREQ
0...600%
4.
LOAD TORQ HIGH
0...600%
0...500 Hz
0...600%
5.
LOAD TORQ HIGH
0...600%
271