8. Internal timer

This application macro is for applications where the motor is
started and stopped with a built-in timer. This macro has also a
boost function which operates the motor after digital input 3
(DI3) has been momentarily activated. An example of the timer
usage is shown below. For further information see chapter
time clock and timed
When using a direct speed reference in the AUTO mode, the
speed reference must be connected to analogue input 1 (AI1)
and the START command is given with digital input 1 (DI1). In
the HAND/OFF mode, the speed reference and START
command are given through the control panel (operator keypad).
If process PI(D) is used, the feedback signal must be connected
to analogue input 2 (AI2). By default, the setpoint is set from the
control panel, but it can also be changed to analogue input 1.
Process PI(D) must be commissioned and adjusted with
parameters
control assistant (recommended).
24:00
22:00
20:00
18:00
16:00
14:00
12:00
10:00
08:00
06:00
04:00
02:00
00:00
110
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
functions.
(Group 40: PROCESS PID SET
Time
Time period 2
period
1
Mon
Tue
Wed
Thu
ACH550-01 User's Manual
1) or using the PID
Time
period
3
Time
period
4
Fri
Sat
Sun
Application macros and wiring
Real-

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ach550

Table of Contents