ACH550-01 User's Manual
Code Description
0113 CTRL LOCATION
Active control location. Alternatives are:
0 =
HAND
1 =
1
EXT
2 =
2
EXT
0114 RUN TIME (R)
Drive's accumulated running time in hours (h)
• Can be reset by pressing the UP and DOWN keys simultaneously
when in the Parameters mode.
0115 KWH COUNTER (R)
Drive's accumulated power consumption in kilowatt hours
The counter value is accumulated till it reaches 65535 after which the
counter rolls over and starts again from 0.
• The counter can be reset by pressing the UP and DOWN keys
simultaneously when in the Parameters mode.
0116 APPL BLK OUTPUT
Application block output signal. Value is from either:
• PFA control, if PFA Control is active, or
• parameter 0112
0118 DI 1-3 STATUS
Status of the three digital inputs
• Status is displayed as a binary number.
• 1 indicates that the input is activated.
• 0 indicates that the input is deactivated.
0119 DI 4-6 STATUS
Status of the three digital inputs
• See parameter 0118
0120 AI 1
Relative value of analogue input 1 in %
0121 AI 2
Relative value of analogue input 2 in %
Parameter listing and descriptions
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
2.
EXTERNAL REF
1
DI
1-3
.
DI
STATUS
Range
0=HAND, 1=EXT1,
2=EXT2
0...9999 h
0...65535 kWh
0...100%
(0...600% for torque)
000...111 (0...7 decimal)
2
3
DI
DI
000...111 (0...7 decimal)
0...100%
0...100%