Code Description
3003 EXTERNAL FAULT 1
Defines the External Fault 1 signal input and the drive response to an
external fault.
0 =
– External fault signal is not used.
NOT SEL
1 =
1 – Defines digital input
DI
• Activating the digital input indicates a fault. The drive displays a fault
(14,
EXT FAULT
2...6 =
2...
DI
DI
input.
• See
1 above.
DI
-1 =
1(
) – Defines an inverted digital input
DI
INV
input.
• De-activating the digital input indicates a fault. The drive displays a
fault (14,
-2...-6 =
2(
DI
INV
as the external fault input.
• See
1(
DI
INV
3004 EXTERNAL FAULT 2
Defines the External Fault 2 signal input and the drive response to an
external fault.
• See parameter 3003 above.
3005 MOT THERM PROT
Defines the drive response to motor overheating.
0 =
– No response and/or motor thermal protection not set up.
NOT SEL
1 =
– Displays an alarm (2010,
FAULT
motor temperature exceeds 90 °C. Displays a fault (9,
) and the drive coasts to stop when the calculated motor
OVERTEMP
temperature exceeds 110 °C.
2 =
– Displays an alarm (2010,
ALARM
motor temperature exceeds 90 °C.
Parameter listing and descriptions
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
1 as the external fault input.
DI
1) and the drive coasts to stop.
6 – Defines digital input
1) and the drive coasts to stop.
EXT FAULT
)...
6(
) – Defines an inverted digital input
DI
INV
) above.
Range
-6...6
2...
6 as the external fault
DI
DI
1 as the external fault
DI
-6...6
0...2
) when the calculated
MOTOR TEMP
MOT
) when the calculated
MOTOR TEMP
2...
6
DI
DI
245