Code Description
5307 EFB CRC ERRORS
Contains a count of the messages with a CRC error received by the
drive. For high counts, check:
• Ambient electro-magnetic noise levels – high noise levels generate
errors.
• CRC calculations for possible errors.
5308 EFB UART ERRORS
Contains a count of the messages with a character error received by the
drive.
5309 EFB STATUS
Contains the status of the EFB protocol.
0 =
– EFB protocol is configured, but not receiving any messages.
IDLE
1 =
EXECUT INIT
2 =
TIME OUT
the network master and the EFB protocol.
3 =
CONFIG ERROR
4 =
-
OFF
LINE
addressed to this drive.
5 =
-
– EFB protocol is receiving messages that are addressed to
ON
LINE
this drive.
6 =
– EFB protocol is performing a hardware reset.
RESET
7 =
LISTEN ONLY
5310 EFB PAR 10
Protocol specific. See manuals Embedded Fieldbus (EFB) Control
(3AFE68320658 [English]) and BACnet® Protocol (3AUA0000004591
[English])
5311 EFB PAR 11
See parameter 5310.
5312 EFB PAR 12
See parameter 5310.
5313 EFB PAR 13
See parameter 5310.
5314 EFB PAR 14
See parameter 5310.
5315 EFB PAR 15
See parameter 5310.
5316 EFB PAR 16
See parameter 5310.
5317 EFB PAR 17
See parameter 5310.
5318 EFB PAR 18
See parameter 5310.
Parameter listing and descriptions
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
– EFB protocol is initializing.
– A time-out has occurred in the communication between
– EFB protocol has a configuration error.
– EFB protocol is receiving messages that are NOT
– EFB protocol is in listen-only mode.
Range
0...65535
0...65535
0...7
0...65535
0...65535
0...65535
0...65535
0...65535
0...65535
0...65535
0...65535
0...65535