Group 51: EXT COMM MODULE
This group defines set-up variables for an external fieldbus
communication module. Refer to the communication module
documentation for more information on these parameters.
Code Description
5101 FBA TYPE
Displays the type of the connected fieldbus adapter module.
0 =
NOT DEFINED
Mechanical installation in the fieldbus user's manual and check that
parameter 9802 is set to 4 = EXT FBA.
1 =
-
Profibus
DP
21 =
on
orks
L
W
32 =
open
CAN
37 =
evice
et
D
N
101 =
ontrol
C
128 =
thernet
E
132 =
PROFINET
135 = E
THER
136 =
EPL - Ethernet POWERLINK
5102
FB PAR 2...FB PAR 26
...
Refer to the communication module documentation for more
5126
information on these parameters.
5127 FBA PAR REFRESH
Validates any changed fieldbus parameter settings.
0 =
– Refreshing done.
DONE
1 =
REFRESH
• After refreshing, the value reverts automatically to
5128 FILE CPI FW REV
Displays the CPI firmware revision of the drive's fieldbus adapter
configuration file. Format is xyz, where:
• x = major revision number
• y = minor revision number
• z = correction number.
Example: 107 = revision 1.07
5129 FILE CONFIG ID
Displays the revision of the drive's fieldbus adapter module's
configuration file identification.
• File configuration information depends on the drive application
program.
5130 FILE CONFIG REV
Contains the revision of the drive's fieldbus adapter module
configuration file.
Example: 1 = revision 1
294
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
– Module not found or not connected. Check chapter
et
N
CAT
– Refreshing.
ACH550-01 User's Manual
Range
0...65535
0=DONE, 1=REFRESH
DONE
0...0xFFFF
0...0xFFFF
0...0xFFFF
Parameter listing and descriptions
.