Circuit breakers
The tables below list ABB circuit breakers that can be used
instead of fuses (recommended). Depending on the type
designation, Tmax moulded case circuit breakers (MCCB) or
S200 B/C miniature circuit breakers (MCB) / manual motor
starters, or both are given.
ABB S200 B/C miniature circuit breakers (MCB) and manual
motor starters
Type
Frame
size
ACH550-
01-
03A3-4
R1
04A1-4
R1
05A4-4
R1
06A9-4
R1
08A8-4
R1
012A-4
R1
015A-4
R2
023A-4
R2
031A-4
R3
038A-4
R3
045A-4
R3
404
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Input
Rated
ABB miniature circuit breakers
current
current
Prospective short circuit current
S200M
B/C
A
A
kA
3.3
10
10
4.1
10
10
5.4
10
10
6.9
16
10
8.8
16
10
11.9
16
10
15.4
20
10
23.0
32
10
31.0
40
10
38.0
50
10
45.0
63
10
ACH550-01 User's Manual
and manual motor starters
S200P
S200
MS325 MS495
B/C
B/C
kA
kA
kA
15
6
15
15
6
15
15
6
15
15
6
15
15
6
15
15
6
15
15
6
15
15
6
15
6
15
6
15
6
Technical data
kA
10
10
10
00577998.xls A