10.3 Ethernet Connection

10.3.1
System configuration for connecting to ControlLogix or CompactLogix
(Ethernet connection type: EtherNet/IP (AB))
ControlLogix,
CompactLogix
PLC
EtherNet/IP
communication
Series
module
1756-ENET(10Mbps)
1756-ENBT(10/
100Mbps)
ControlLogix
1756-EN2TR(10/
100Mbps)
1756-EN2T (10/
100Mbps)
CompactLogix
-
*1
*2
*3
*4
*5
*6
10 - 18
10.3 Ethernet Connection
EtherNet/IP
communication
module
Communication
Type
*1
*4
*4
Ethernet
*4
*4
Ethernet
Allen-Bradley product manufactured by Rockwell Automation, Inc. For details of the product, contact Rockwell Automation, Inc.
The destination connected with the twisted pair cable varies with the configuration of the applicable Ethernet network system.
Connect to the Ethernet module, hub, transceiver or other system equipment corresponding to the applicable Ethernet network
system.
Use cables, connectors, and hubs that meet the IEEE802.3 10BASE-T/100BASE-TX standards.
A length between a hub and a node.
The maximum distance differs depending on the Ethernet device to be used.
The following shows the number of the connectable nodes when a repeater hub is used.
• 10BASE-T: Max. 4 nodes for a cascade connection (500m)
• 100BASE-TX: Max. 2 nodes for a cascade connection (205m)
When switching hubs are used, the cascade connection between the switching hubs has no logical limit for the number of
cascades.
For the limit, contact the switching hub manufacturer.
The connectable EtherNet/IP communication module differs depending on the PLC series.
(ControlLogix5550/5555/5560)
1756-ENET(10Mbps), 1756-ENBT(10/100Mbps), 1756-EN2T (10/100Mbps) (1756-L64 only correspondence)
(ControlLogix5570)
1756-EN2TR(10/100Mbps)
The number of the connectable GOTs for 1 PLC differs depending on the PLC series.
(ControlLogix5550/5555/5560)
• When PLC:GOT is N:1, the following number of the PLCs can be connected to 1 GOT.
TCP: 128 or less
When PLC:GOT is 1:N, the following number of the GOTs can be connected to 1 PLC.
TCP: 64 or less (recommended to 16 or less)
(ControlLogix5570)
• When PLC:GOT is N:1, the following number of the PLCs can be connected to 1 GOT.
TCP: 128 or less
When PLC:GOT is 1:N, the following number of the GOTs can be connected to 1 PLC.
TCP: 128 or less (recommended to 16 or less)
GT25-W, GT2505-V does not support the option device.
Connection cable
Connection cable
Maximum
segment
*2
Cable model
length
100m
• 10BASE-T
Shielded twisted
pair cable (STP) or
unshielded twisted
pair cable (UTP) of
category 5 or higher
• 100BASE-TX
Shielded twisted
pair cable (STP) or
unshielded twisted
pair cable (UTP) of
category 3 or higher
100m
GOT
GOT
*6
Option device
Model
*3
- (Built into GOT)
GT25-J71E71-
100
- (Built into GOT)
GT25-J71E71-
100
Communication driver
EtherNet/IP(AB), Gateway
Number of connectable
equipment
*4
*5
When PLC:GOT is N:1
TCP: 128 PLCs or less
for 1 GOT
When PLC:GOT is 1:N
TCP: 32 GOTs or less
(recommended to 16 or
less) for 1 PLC