■4. Data interval extension time settings
Set the data interval extension time as the following procedure.
Step 1.
Turn the power of the module OFF.
Step 2.
Set the DIP switch 4 and 6 to ON and 5 to OFF.
Step 3.
Set the data interval extension time using the rotary switch (address setting switch).
For the setting method, refer to the following.
■3. Module address settings
Step 4.
Turn the power of the module ON.
The FAIL/RUN lamp lights in green and the set time becomes valid.
Step 5.
Turn the power of the module OFF again and set the DIP switches and rotary switch to the original position.
9.5.16

Connecting to SB1

■1. Communication settings
Make the communication settings of SB1 using the switch key on the front surface.
For the operation procedure, refer to the SB1 manual.
Item
*2
Communication protocol
*1*3
Device address
(Slave address)
*1*4
Communication speed
*1*5
Data bit configuration
*6
Interval time
*1
Adjust the settings with GOT settings.
*2
Select 1: MODBUS.
*3
When the setting value is 0, communication is not performed.
*4
The communication speed cannot be set to 2400bps or 4800bps on the GOT side.
Select 2 or 3.
*5
For details on the data bit configuration, refer to the following.
*6
Set the maximum time from when the last character stop bit is sent from the GOT side until the transmission cable becomes
ready to receive.
0: RKC communication
1: MODBUS
0 to 99
0: 2400bps
1: 4800bps
2: 9600bps
3: 19200bps
0 to 5
0 to 250ms
Set value
Data bit
0
8
1
8
2
8
3
8
4
8
5
8
Setting range
Parity bit
None
None
Even
Even
Odd
Odd
9.5 Temperature Controller Side Setting
9
Stop bit
1
2
1
2
1
2
9 - 59