Mitsubishi Electric GOT2000 Series Connection Manual page 460

Graphic operation terminal
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

■4. Ethernet setting
(1) Ethernet connection type: FETCH/WRITE
This section describes the Ethernet setting for the communication driver SIEMENS S7 (Ethernet).
Item
Host
Net No.
*1
Station
Unit Type
IP Address
FETCH Port No.
WRITE Port No.
Communication
*1
15 - 18
15.3 Ethernet Connection
The host is displayed. (The host is indicated with an asterisk (*).)
Set the network No. of the connected Ethernet module.
(Default: blank)
Set the station No. of the connected Ethernet module.
(Default: blank)
SIEMENS S7 (fixed)
Set the IP address of the connected Ethernet module.
(Default: blank)
Set the FETCH port No. of the connected Ethernet module.
(Default: 2000)
For the WRITE port No. of the connected Ethernet module, the value that
the FETCH port No. is incremented by one is set automatically.
(Default: 2001)
TCP (fixed)
Each of [GOT Station] set in the communication detail setting and [Station] set in the Ethernet setting must be set to different
station numbers.
■2. Communication detail settings
Description
Set value
1 to 239
1 to 64
SIEMENS S7
(fixed)
PLC side IP address
1024 to 65534
1025 to 65535
TCP (fixed)

Advertisement

Table of Contents
loading

Table of Contents