■2. Communication detail settings
Make the settings according to the usage environment.
(1) SIEMENS S7-300/400
Item
*2
Transmission Speed
Data Bit
Stop Bit
Parity
*1*2
Adapter Address
*1*2
Host Address
*1
Set the address without overlapping the address of other units.
*2
The GOT automatically sets the values of Transmission Speed, Adapter Address, and Host Address to the HMI Adapter.
Description
Set this item when change the transmission speed used for
communication with the connected equipment.
(Default: 38400bps)
Set this item when change the data length used for communication with
the connected equipment.
(Default: 8bit)
Specify the stop bit length for communications.
(Default: 1bit)
Specify whether or not to perform a parity check, and how it is performed
during communication.
(Default: Odd)
Specify the adapter address (station No. of the adapter to which the GOT
is connected) in the connected network.
(Default: 1)
Specify the host address (station No. of the PLC that the GOT will monitor)
in the connected network.
(Default: 2)
Range
9600bps,
19200bps,
38400bps
8bit (fixed)
1bit (fixed)
Odd (fixed)
1 to 31
1 to 31
15.2 Serial Connection
15
15 - 9