GOOSE CONFIGURATION VIA THE 3 SERIES MENUS

GOOSE configuration via the 3 Series menus
IEC61850 Feature
Manufacturing Message Specification (MMS)
standard ISO/IEC 9506
GOOSE Transmission of analog values
GOOSE Reception of analog values
GOOSE Configuration storage
File system to maintain ICD/CID files
4-2
message from one of the feeders (in this case feeder A) within a specified period of time
after detection of the overcurrent fault, the 345 will trip its breaker, removing power to the
bus. If however, a GOOSE message is received from any one of the feeder relays, the 345
will delay the trip of its breaker long enough for the downstream feeder to remove the
fault.
Configuration of GOOSE messaging within the 3 Series family of relays can be
accomplished in one of three ways:
Users familiar with both the 3 Series configuration menus and IEC61850
implementation within the 3 Series, may prefer to configure the relays directly
through the menus.
For those not familiar with the 3 Series IEC61850 implementation and/or the 3 Series
menus, the 3 Series simplified GOOSE message tool may save time and effort.
For those interested in a more IEC61850-centric approach, the IEC61850 configurator
tool may be used.
The 3 Series relay firmware supports IEC61850 GOOSE communications on the optional
communications daughter board.
Portions of the IEC61850 standard not pertaining to GOOSE, are not implemented in the 3
Series relay depending on order code and GOOSE type setting (found under
SETUP > COMMUNICATIONS > GOOSE CONFIGURATION > GENERAL SETTINGS
Order Code includes
"IEC61850" & GOOSE Type
is "Simplified"
Not Available
Not Available
Not Available
MODBUS Set Points
Not Available
Configuration of transmission and reception settings for the GOOSE feature are performed
using EnerVista SR3 Setup Software.
The 3 Series relay firmware accepts GOOSE messages from UR, F650 and UR Plus. The
interoperability with other manufacturers will be guaranteed in almost all cases, by
implementing the reception side with nested structures (one level of nesting) and all the
standard data types.
GOOSE settings changes will take effect only after the 3 Series relay is re-booted. One
setting is available to Enable/Disable both Transmission and Reception. It is possible to
change these settings from the Front Panel of the relay.
CHAPTER 4: 3 SERIES IEC61850 GOOSE
Order Code includes
"IEC61850" & GOOSE Type
is "Advanced"
Available
Available
Not Available
CID file and MODBUS Set
Points
Available
SR3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE
S1 RELAY
).
Order Code includes
"IEC61850 GOOSE"
(and not "IEC61850")
Not Available
Not Available
Not Available
MODBUS Set Points
Not Available