GE 350 Communications Manual page 106

Protective relay platform
Hide thumbs Also See for 350:
Table of Contents

Advertisement

USING THE IEC 61850 CONFIGURATOR
4-34
1.5.
Enter an optional device name.
1.6.
Set the interface to Ethernet and enter the first relays IP address, and Slave
address.
1.7.
To verify communications and ensure the correct order code is entered, select
Read Order Code.
1.8.
After a brief period of time the software program should read the relay's order
code and fill it in within the work area. If the software fails to connect to the
relay and read the order code, an error message will appear indicating that
either the relay was not connected to the network correctly, or the IP address,
subnet mask and/or the ModBus Slave address entered in the software does
not match the relay. Troubleshoot accordingly.
SR3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE