GE 350 Communications Manual page 98

Protective relay platform
Hide thumbs Also See for 350:
Table of Contents

Advertisement

USING THE SIMPLIFIED GOOSE CONFIGURATOR
4-26
4.1.
Right-click the settings file labeled 228_GOOSE7 and select Write Setting File
to Device. This action launches a second window showing all devices
configured for the online window. To start the download process to Relay 228,
click Relay 228 such that it is highlighted, then select Send.
4.2.
Once the download is complete, repeat the process for the setting file labeled
230_GOOSE7 and relay 230. At this point the GOOSE messaging configuration
is complete.
4.3.
To test the GOOSE messaging first, open the Virtual Input Commands window
of Relay 228, then under 230's Actual Values branch, open the Output Relays
window.
Force Virtual Input number 1 of 228 on or off and monitor the status of Relay 3 in
Relay 230. Note that the status of Relay 3 follows the status of Virtual Input 1 of Relay
228.
This completes the exercise.