CHAPTER 4: 3 SERIES IEC61850 GOOSE
SR3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE
Relay 228's GOOSE message TX1's structure must be known by all relays receiving
this message. The structure of GOOSE TX1 is contained within relay 228's CID file.
To load this structure into relay 254 proceed as follows:
3.3.
From the main 3 Series menu, right-click relay 254 and select IEC61850 Device
Configurator, then select GOOSE Reception.
3.4.
To load the structure of TX1 into relay 254, select ADD IED, then select the
name of the file containing relay 228's CID file which, in our example, is
228_Lab_1.CID, then select Open.
USING THE IEC 61850 CONFIGURATOR
4-41