350 MODBUS MEMORY MAP
Modbus
Hex
Description
Address
Address
EVENT RECORDER
40649
0x288
Recording of Block Events
40654
0x28D
Recording of Pickup Events
40655
0x28E
Recording of Contact Input
Events
40656
0x28F
Recording of Virtual Input
Events
40657
0x290
Recording of Remote Inputs 0
40658
0x291
Recording of Logic Element
Events
40660
0x293
Recording of Trip Events
40661
0x294
Recording of Alarm Events
40662
0x295
Recording of Control Events 0
40665
0x298
Recording of Dropout Events 0
40666
0x299
Recording of Set Time/Date
Events
40667
0x29A
Event Record Selector
THERMAL PROTECTION
40699
0x2BA
Thermal O/L Curve
TEMPERATURE
40820
0x333
Enable Ambient Temp
40821
0x334
HI Alarm Level
40822
0x335
Low Alarm Level
40823
0x336
Hysteresis Level
40824
0x337
Time Delay
40825
0x338
Output Relays
TRANSIENT RECORDER
40668
0x29B
Trigger on Pickup
40669
0x29C
Trigger on Dropout
40670
0x29D
Trigger on Alarm
40671
0x29E
Trigger on Dropout
40672
0x29F
Trace Memory Channel
Selector
40673
0x2A0
Trace Memory Buffer
Selector
40674
0x2A1
Trace Memory Sample Index 0
40676
0x2A3
Trace Memory Trigger
Position
40677
0x2A4
Trigger Mode
40678
0x2A5
Number of Records
40887
0x376
Transient Sampling Rate
VT FUSE FAIL
40908
0x38B
VT Fuse Fail
RELAY STATUS
40927
0x39E
Relay Status
CONTACT INPUT NAMES (1 TO 8)
40961
0x3C0
Input Name 1
12-24
CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES
Min
Max
0
1
0
1
0
1
0
1
1
0
1
0
1
0
1
1
1
0
1
1
65535
0
2
0
2
20
80
-40
20
2
10
1
60
0
0x7F
0
1
0
1
0
1
0
1
0
16
0
10
6144
0
100
0
1
0
2
0
3
0
2
0
1
0
7
SR3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE
Step Units
Format
Factory
Code
Default
1
---
FC126
1
1
---
FC126
0
1
---
FC126
1
1
---
FC126
1
1
---
FC126
1
1
---
FC126
1
1
---
FC126
1
1
---
FC126
1
1
---
FC126
1
1
---
FC126
0
1
---
FC126
0
1
---
F1
1
1
---
FC236
0
1
---
FC206
0
1
°C
F1
60
1
°C
F4
10
1
°C
F1
2
1
min
F1
1
1
---
FC198
0
1
---
FC103
0
1
---
FC103
0
1
---
FC103
0
1
---
FC103
0
1
---
F26
0
1
---
F1
0
1
---
F1
0
1
%
F1
20
1
---
FC148
0
1
---
F95
0
1
---
FC429
0
1
---
FC140
0
1
---
F99
0
1
---
F22
52a
Contact
Size in
words
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
7