USING THE SIMPLIFIED GOOSE CONFIGURATOR
4-22
At the bottom of the screen there is a selection to determine if quality bits are to be
included with the value. Users have an option to Enable/Disable Quality here. In our
example application we are going to send just the status of Virtual Input 1 from the
relay labeled 228 to the relay labeled 230, so the Value Only selection will be made by
clicking on that portion of the screen.
Also located at the bottom of the screen are the icons the restore Restore and Default:
Restore if selected will restore the screen to the last save position
Default if selected will set all the screen information to default values.
To configure Relay228_GOOSE7 to transmit Virtual Input 1 proceed as follows:
SR3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE
CHAPTER 4: 3 SERIES IEC61850 GOOSE