CHAPTER 3: ETHERNET INTERFACE
Fault Report Mapping
Disabled
Enabled
SR3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE
350 and 339
Some fault report data has been scaled to fit into a 16-bit value as follows:
Fault Report Data
Fault Report Ia, Ib, Ic, Ia2, Ib2, Ic2
Fault Report Ig, Ig2
Fault Report In , In2
Fault Report Va, Vb, Vc, Vab, Vbc, Vca, Vn Format_F9 * 10000 /( BusVTRatio * BusVTSecondary)
Fault Report Vaux
Fault Report System Frequency
Fault Report Phases
DNP ETHERNET PROTOCOL SETTINGS
Fault Report Mapping
Disabled
Enabled
1
40
...
...
...
...
31
70
Scale
Format_F10 * 100 / CT Primary
Format_F10 * 100 / Gnd CT Primary
Format_F10 * 100 / CT Primary
Format_F9 * 10000 /( AuxVTRatio * AuxVTSecondary)
Format_F3
Format_F37
345
Analog Input Point 1 Entry
...
...
Analog Input Point 31 Entry
3-21