CHAPTER 4: 3 SERIES IEC61850 GOOSE
NOTE:
SR3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE
The simplified GOOSE Configuration Tool required all settings files to be present before
launching the tool. If at a later date settings files need to be added or removed, the
above process must be repeated from the beginning.
3.2.
In the Transmission Device column expand the tree of 228_GOOSE7 such that
Virtual input 1 is displayed. Left-click Virtual Input 1 in the Transmission
Device column and drag this point into the relay(s) that are to receive the status
of this point.
In our example we would left-click Virtual Input 1 and drag it into the Reception
column corresponding to the relay labeled 230_GOOSE7. In this case we dragged
Virtual Input 1 from the relay labeled 228_GOOSE7 into the first row of relay
230_GOOSE7. This position corresponds to Remote Input 1. This is the process that is
used to configured both the transmission and reception. Once the configuration is
complete, select Save. The SGC program then takes the information within the screen
and determines how to set up the transmission and reception list for each device.
USING THE SIMPLIFIED GOOSE CONFIGURATOR