Table 4-1: Calculate Min/Max MMXU Node Values
MMXU Node
To Calculate
TotW
Max (350)= (Phase CT Primary * 115 A ) * (Phase VT Ratio * BusVTRatio * 240 V)
TotVar
*(scale W/kW/MW)
TotVA
Max(339) = (Phase CT Primary * 115 A ) * (Phase VT Ratio * BusVTRatio * 240 V)
*(scale W/kW/MW)
Max(339 two speed) = (SpeedTwoPhase CT Primary * 115 A ) * (Phase VT Ratio
* BusVTRatio * 240 V) *scaleW/kW/MW
min = -max
TotPF
max = 1
min = -1
Hz
max = 80
min = 30
Hte
max = 15
min = -15
PPV
max = BusVTRatio * 240 V
min = 0
PhV
max = BusVTRatio * 240 V
min = 0
A$phsA
Max(350,345) = (Phase CT Primary * 115A)
A$phsB
Max(339) = (Phase CT Primary * 115A)
A$phsC
Max(339 two speed) = (SpeedTwoPhase CT Primary * 115 A)
min = 0
A$neut
Max(350) = (Ground CT Primary * 115A)
Max(350 SG) = (SensitiveGround CT Primary * 115A)
Max(339) = (Ground CT Primary * 115A)
Max(339 SG) = (SensitiveGround CT Primary * 115A)
Max(339CBCT) = 15
min = 0
A$net
Max(350,345) = (Phase CT Primary * 115A)
Max(339) = (Phase CT Primary * 115A)
Max(339 two speed) = (SpeedTwoPhase CT Primary * 115 A)
min = 0
A$res
Max = (Ground CT Primary * 115A)
Max(SG) = (SensitiveGround CT Primary * 115A)
min = 0
AuxV
max = AuxVTRatio * 240V
min = 0
SeqA$c1, c2 ,c3
Max(350,345) = (Phase CT Primary * 115A)
Max(339) = (Phase CT Primary * 115A)
Max(339 two speed) = (SpeedTwoPhase CT Primary * 115 A)
min = 0
SeqV$c1,c2,c3
max = (BusVTRatio * 240)
min = 0
dbAng
angle dB = (DB percentage* 360)
GGIO3 Logical Node
Range: Enum
These are the control models supported: (0) status only, (1) direct-with-normal-
security.
XCBR Logical Node
Range: Enum for ctlModel and 500:60000ms for sboTimeout
The IEC61850 "operate" command must be executed after "select" command within
the XCBR1 pos sboTimeout setting value to be successful.
XCBR1 pos cltModel can be configured as (0)status only, (1) direct-with-nomal-
security, (2)sbo-with-normal-security, (3)direct-with-enhanced-security,(4)sbo-with-
enhanced-security