IEC 60870-5-103 SERIAL COMMUNICATION
2-24
Modbus Address
Description
44388
First ASDU First Analogue Entry
44389
First ASDU First Analogue Factor
44390
First ASDU First Analogue Offset
44391
First ASDU Second Analogue Entry
44392
First ASDU Second Analogue Factor
44393
First ASDU Second Analogue Offset
.........
44412
First ASDU Ninth Analogue Entry
44413
First ASDU Ninth Analogue Factor
44414
First ASDU Ninth Analogue Offset
44415
Second ASDU Identification Type
44416
Second ASDU Function Type
44417
Second ASDU Information Number
44418
Second ASDU Scan Timeout
44419
Second ASDU First Analogue Entry
44420
Second ASDU First Analogue Factor
44421
Second ASDU First Analogue Offset
.....
44443
Second ASDU Ninth Analogue Entry
44444
Second ASDU Ninth Analogue Factor
44445
Second ASDU Ninth Analogue Offset
44446
Third ASDU Identification Type
......
44476
Third ASDU Ninth Analogue Offset
44477
Fourth ASDU Identification Type
......
44507
Third ASDU Ninth Analogue Offset
In the measurands configuration screen, with each selected measurement, a Factor and
an Offset must be configured.
The Factor is a multiplier factor.
The Offset is an offset factor to be applied to the relay measurement to make the final
measurement calculation to be sent to the master
The factor and offset parameters allow the user to perform different scaling in the relay
measurements. The final measurement sent to the IEC103 master will be: "a*x+b", where
"x" is the relay measurement, "a" is the multiplier factor and "b" is the offset.
The measurands will be sent to the primary station as a response to a class 2 request.
There is a Timeout configurable with increments of 100 ms, between 0 and 60 min, in order
to configure the desired interval.
SR3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE
CHAPTER 2: RS485 INTERFACE
Value
Format
Disabled
F88
1
F3
0
F1
Disabled
F88
1
F3
0
F1
Disabled
F88
1
F3
0
F1
3 or 9
F221
<0 - 255 >
F1
< 0 - 255 >
F1
< 0 - 1000> secs
F1
Disabled
1
F3
0
F1
Disabled
1
F3
0
F1
3 or 9
F221
0
F1
3 or 9
F221
0
F1