2.5 TECHNICAL SPECIFICATIONS
2.5.7 Real time clock
Accuracy: .....................................................................................typical ±20 ppm
Backup Energy: .........................................................................more than 1 week
Note: For relay versions before 7.00, when the relay date and time is changed using any documented methods (Modbus, IRIG-B, SNTP,
Front Panel...) the relay acknowledges and updates the time instantly but it takes nearly 3 minutes for the new time to be permanently
stored in the Real Time Clock's NVRAM.
2.5.8 Outputs
OUTPUTS
Single Contact Carry continuous:.....................................16 A
Make and Carry for 1 s: .........................................................60 A
Break at L/R of 40 ms: ............................................................0.3 A DC max. at 125 Vdc
Operate Time: ............................................................................< 8 ms
Contact Material: ......................................................................silver alloy
Output Logic Type, Output Type and Pulse Output Time are selectable by setting for each output
Output Logic Type:...................................................................positive/negative
Output Type: ...............................................................................normal/pulse/latch (selectable by setting for each output)
Pulse Output Time: ..................................................................0 to 60000 ms in steps of 1 ms (applicable only to signals sent as pulse type)
Separate operate and reset signals can be configured by any digital signal programmable through the PLC
Contact Outputs (F31-F33, F34-F36) for board type
2 (supervision) in slot F: ....................................................The current seal-in circuit is used for verifying the current condition in a circuit during
REMOTE OUTPUTS (IEC61850 GSSE/GOOSE)
Standard Output Points: ........................................................32
User Output Points:..................................................................32
2.5.9 Control power supply
LOW RANGE (LO)
Nominal DC Voltage:
Min/Max DC Voltage
Note:
Voltage Loss hold-up time:(*)
(*) These figures have been calculated for models with the following characteristic:
- IEC Symbols Graphic display
- Rear Ethernet Communication Board 2: PRP, 1588, 10/100 Base TX+ Redundant 100 Base FX
- F and G I/O Board:
Slot F: 8 Digital Inputs + 8 Outputs + 2 Trip / Close circuit supervision circuits
Slot G: 16 Digital Inputs + 8 Outputs
HIGH RANGE (HI)
Nominal DC Voltage:
Min/Max DC Voltage
Nominal AC Voltage:
Min/Max AC Voltage:
Voltage Loss Hold-up Time:
2-24
0.25 A DC max. at 250 Vdc
the time that the tripping contact remains closed. If the current in the tripping circuit is
maintained over 500 mA, the function is sealed independently of the status of the
function that caused the trip.
24 to 48 V
19.2 / 57.6 V
Low range is DC only
24 Vdc 30 ms
48 Vdc 100 ms
110 to 250 V
88 / 300 V
120 to 230 V
102 / 250 V
200 ms typical
100 ms worst case
F650 DIGITAL BAY CONTROLLER
ALL RANGES
Power Consumption:
Typical =25 VA, Maximum =45 VA
Display backlight auto power-off mode after 15 minutes without touching
any key, in order to ensure long life and
minimum consumption
INTERNAL FUSE
V:
250 VAC
I:
2.5A
Size:
5 x 20 mm
Type:
Quick acting (F)
UL listed miniature Fuse
CHAPTER 2: PRODUCT DESCRIPTION
GEK-113000-AF