GE
Grid Solutions
F650 Digital Bay Controller
Chapter 2: Product Description

PRODUCT DESCRIPTION

2.1 F650 Overview

F650 is a protection, control, monitoring, metering and registering unit, suitable for many different applications, such as
main protection for distribution feeders and transmission lines, as well as backup protection for transformers, busbars,
capacitor banks, etc.
Overvoltage and undervoltage protection, overfrequency and underfrequency protection, breaker failure protection,
directional current supervision fault diagnostics and programmable logic functions are provided.
This relay also provides phase, neutral, ground and sensitive ground, instantaneous and time overcurrent protection. The
time overcurrent function provides multiple curve shapes or FlexCurves™ for optimum co-ordination. Automatic reclosing,
synchrocheck, and line fault locator features are also provided.
Voltage, current, power, and energy metering is built into the relay as a standard feature. Current parameters are
available as true RMS magnitude, or as RMS magnitude of undamental frequency and angle (phasor).
Diagnostic features include a sequence of records. The internal clock used for time-tagging can be synchronized with an
IRIG-B signal or via SNTP, DNP or Modbus protocol over the Ethernet port. From firmware version 7.00 and above, IEEE
1588 time protocol is also available. Precise time stamping allows the sequence of events to be determined throughout the
system. Oscillography data capture may be set to record the measured parameters before and after the event for viewing
on a personal computer (PC). These tools significantly reduce troubleshooting time and simplify report generation in the
event of a system fault.
A faceplate RS232 or USB port may be used to connect to a PC for programming settings and monitoring actual values.
A variety of communications modules are available. Two rear RS485 ports allow independent access by operating and
engineering personnel. All serial ports use the Modbus
100BaseFX Ethernet interface which can be used to provide fast, reliable communications in noisy environments.
GEK-113000-AF
RTU protocol. Optional communications modules include a
®
F650 DIGITAL BAY CONTROLLER