CHAPTER 5: BOOTCODE AND FIRMWARE UPGRADE

5.1.1 Communication parameters

1.
Ethernet Connection/Type - Both boot code and firmware upgrade processes require Ethernet communications. It is
strongly recommended to use a direct connection between the PC and the relay using a Cross-Over RJ45 Ethernet
cable, instead a direct connection through a hub or switch. Upgrading through Local Area Network (LAN) must be
avoided.
Serial RS232 Communication - Serial communication is necessary only to perform the bootware upgrade for versions
previous to 7.00.
2.
Relay IP Address - An IP address must be assigned to the relay in the Ethernet parameters via HMI at Product Setup >
Communication > Ethernet > Ethernet1 menu, or via Enervista 650 Setup software at Setpoint > Product Setup >
Communication Settings > Network (Ethernet) 1 as shown in the table below:
Table 5-1: Ethernet parameters
Product Setup > Communication Settings > Network (Ethernet) 1
Name
IP Address Oct1
IP Address Oct2
IP Address Oct3
IP Address Oct4
Netmask Oct1
Netmask Oct2
Netmask Oct3
Netmask Oct4
Gateway IP Oct1
Gateway IP Oct2
Gateway IP Oct3
Gateway IP Oct4
3.
PC IP Address - In case the boot code has been previously updated to the relay (section 9.2), the IP address and other
parameters already assigned in the process are:
IP Address:192.168.37.177
Netmask:255.255.255.0
Gateway:192.168.37.10
Then the PC settings should be the same pattern as follows:
IP Address:192.168.37.xxx
Netmask:255.255.255.0
Gateway:192.168.37.10 (if desired)
Where XXX is a number between 0 and 255 that is not assigned to any other device to avoid collisions.
4.
Other Network, Communications and Data Flow checks
According to the model number of the relay, to enable the 10/100 BASE TX-CABLE option in the relay communication
board, a specific jumper in this board must be changed. See detailed instructions in paragraph 3.4.3 of Instruction
Manual GEK-106310AE.
IP address, netmask, gateway are correct and match the parameters used in the computer to perform the procedure.
See table 9.1 (on this chapter) of Manual GEK-106310AE COMMUNICATION PARAMETERS.
GEK-113000-AF
Value
Units
192
168
37
177
255
255
255
0
192
168
37
10
F650 DIGITAL BAY CONTROLLER
5.1 FIRMWARE UPGRADE VERSIONS BELOW 7.00.
Range
[0 : 255]
[0 : 255]
[0 : 255]
[0 : 255]
[0 : 255]
[0 : 255]
[0 : 255]
[0 : 255]
[0 : 255]
[0 : 255]
[0 : 255]
[0 : 255]
5-3