11.4 GOT Side Settings

11.4.1
Setting communication
interface (Communication
settings)
Set the channel of the equipment to be connected to the
GOT.
2.
1.
Select [Common]
[Controller Setting] from the
menu.
2.
The Controller Setting window is displayed. Select the
channel to be used from the list menu.
3.
Set the following items.
• Manufacturer: CHINO
• Controller Type: CHINO Controllers
• I/F: Interface to be used
• Driver: CHINO Controller(MODBUS)
4.
The detailed setting is displayed after Manufacturer,
Controller Type, I/F, and Driver are set.
Make the settings according to the usage
environment.
11.4.2 Communication detail settings
Click the [OK] button when settings are completed.
POINT
POINT
POINT
The settings of connecting equipment can be
confirmed in [I/F Communication Setting].
For details, refer to the following.
1.1.2 I/F communication setting
Make the settings according to the usage environment.
3.
4.
Transmission
Speed
Data Bit
Click!
Stop Bit
Parity
Retry
Timeout Time
Host Address
Delay Time
Format
11. CONNECTION TO CHINO CONTROLLER
11.4.2 Communication detail settings
Item
Description
Set this item when change the
transmission speed used for
communication with the connected
equipment.
(Default: 9600bps)
Set this item when change the data
length used for communication
with the connected equipment.
(Default: 8bits)
Specify the stop bit length for
communications.
(Default: 1bit)
Specify whether or not to perform a
parity check, and how it is
performed during communication.
(Default: None)
Set the number of retries to be
performed when a communication
error occurs.
(Default: 3times)
Set the time period for a
communication to time out.
(Default: 1sec)
Specify the host address (station
No. of the GOT to which the
controller is connected) in the
connected network.
(Default: 1)
Set this item to adjust the
transmission timing of the
communication request from the
GOT.
(Default: 5ms)
Select the communication format.
(Default: 1)
Format 1:
Accessible to LT230/300/400/830,
DZ1000/2000, Not accessible to
GT120
Format 2:
Accessible to GT120
11.4 GOT Side Settings
Range
9600bps,
19200bps,
38400bps,
57600bps,
115200bps
7bits/8bits
1bit/2bits
None
Even
Odd
0 to 5times
11
1 to 30sec
1 to 99
0 to 300ms
1/2
11 - 23