9.5 PLC Side Setting

POINT
POINT
POINT
SHARP PLC
For details of the SHARP PLC, refer to the following
manual.
SHARP PLC user's Manual
Model name
JW-22CU
JW-32CUH,
JW-33CUH
PLC CPU
JW-70CUH,
JW-100CUH,
JW-100CU
Z-512J
JW-21CM
Link unit
JW-10CM,
ZW-10CM
9.5.1
System memory setting
Set the system memory.
System
Refer to
memory No.
9.5.1
9.5.2
9.5.1
#236
9.5.2
9.5.3
9.5.4
#237
*1
*2
Terminating resistor setting switch (For JW-
22CU only)
Set the terminating resistor setting switch.
(1) When using KV-L20R or KV-L20
terminator switch(SW1)
ON
OFF
9. CONNECTION TO SHARP PLC
Connecting to JW-22CU, JW-
70CUH, JW-100CUH or JW-
100CU
Item
Set value
D7 D6 D5 D4 D3 D2 to D0
0
0 (3)
Transmission speed
(1)
Transmission
000: 19200bps
speed,
001: 9600bps
parity and
010: 4800bps
stop bit
(2)
Parity
10 (fixed): Even
(3)
Stop bit
1 (fixed): 2 bits
Station No.
1: Station No. 1 (fixed)
Indicates only the transmission speeds that can be set on
the GOT side.
Set the same transmission speed of the GOT.
For the transmission speed setting on the GOT side, refer to
the following.
9.4.1 Setting communication interface
(Communication settings)
Settings
For RS-232
RS-422 communication
communication
OFF (no terminating
ON (terminating resistor
resistor)
9.5 PLC Side Setting
(2)
(1)
*1
*2
9
attached)
9 - 11