10.4 GOT Side Settings

10.4.1 Setting communication
interface (Communication
settings)
Set the channel of the equipment to be connected to the
GOT.
2.
1.
Select [Common]
[Controller Setting] from the
menu.
2.
The Controller Setting window is displayed. Select the
channel to be used from the list menu.
3.
Set the following items.
• Manufacturer: Shinko Technos
• Controller Type: Shinko Technos Controller
• I/F: Interface to be used
• Driver: Shinko Technos Controller
4.
The detailed setting is displayed after Manufacturer,
Controller Type, I/F, and Driver are set.
Make the settings according to the usage
environment.
10.4.2 Communication detail settings
Click the [OK] button when settings are completed.
POINT
POINT
POINT
The settings of connecting equipment can be
confirmed in [I/F Communication Setting].
For details, refer to the following.
1.1.2 I/F communication setting
3.
4.
Click!
10. CONNECTION TO SHINKO TECHNOS INDICATING CONTROLLER
10.4.2 Communication detail settings
Make the settings according to the usage environment.
Item
Description
Set this item when change the
Transmission
transmission speed used for
Speed
communication with the connected
equipment. (Default: 9600bps)
Set this item when change the data
length used for communication
Data Bit
with the connected equipment.
(Default: 7bits)
Specify the stop bit length for
Stop Bit
communications. (Default: 1bit)
Specify whether or not to perform a
parity check, and how it is
Parity
performed during communication.
(Default: Even)
Set the number of retries to be
Retry
performed when a communication
error occurs. (Default: 0time)
Set the time period for a
Timeout Time
communication to time out.
(Default: 3sec)
Specify the host address (station
No. of the GOT to which the
Host Address
indicating controller is connected)
in the connected network.
(Default: 0)
Set this item to adjust the
transmission timing of the
Delay Time
communication request from the
GOT. (Default: 5ms)
POINT
POINT
POINT
(1) Communication interface setting by the Utility
The communication interface setting can be
changed on the Utility's [Communication Settings]
after writing [Communication Settings] of project
data.
For details on the Utility, refer to the following
manual.
GOT2000 Series User's Manual (Utility)
(2) Precedence in communication settings
When settings are made by GT Designer3 or the
Utility, the latest setting is effective.
10.4 GOT Side Settings
Range
9600bps,
19200bps,
38400bps,
57600bps,
115200bps
7bits/8bits
1bit/2bits
None
Even
Odd
0 to 5times
3 to 30sec
10
0 to 94
0 to 300ms