01 Enter Zn No.
12
01 Output Action
Close for 2 sec
1
Enter Output No.
R02
02
02
A E P TRIG
R02 1 1
3 ZL=00

About Zone Lists (*81 Menu Mode)

Zone lists let you group individual zones for use with certain system actions. The following table shows the
available zone lists and their purposes:
List No.
Used for...
1, 2
general purpose (GP)
3
chime-by-zone
4
cross zones (see note at right)
5
night stay zones
6
general purpose
: dial delay disable
V21iPSIA
7
general purpose
: unlimited reports
V21iPSIA
8
general purpose
9
zones that activate Pager 1
10
zones that activate Pager 2
11
zones that activate Pager 3
12
zones that activate Pager 4
Zone Number
(prompt appears if zone number was selected)
Enter the desired zone number associated with this output number.
Press [ ✱ ] to continue.
Enter the zone event that will activate this output.
01 Enter Event
Restore
0
Press [ ✱ ] to continue to the "Output Action" prompt
Output Action
0 = off
1 = Close for 2 seconds
2 = Stay Closed
3 = Pulse on & off (1 sec ON, 1 sec OFF)
Enter the desired device action as listed above. Press the [ ✱ ] key to continue.
Output Number
01-16 = output no.; 17-18 = on-board triggers
Enter the device output number (programmed in *79 Menu Mode) you want associated with
this output. Press [ ✱ ] to continue.
Summary Screen
A summary screen appears showing the programmed settings.
Press [ ✱ ] to continue.
(see field *26 to enable option)
0 = restore; 1 = alarm/fault/trouble
4 = Change Device State
5 = Duration 1 (see data field *177)
6 = Duration 2 (see data field *177)
Notes
• Any list may include any or all of the system's zone
numbers.
• A zone list can be assigned to more than one output relay.
• Zone List 4: When creating zone list 4 for cross zoning,
include only zones assigned to zone types 3, 4, or 5. Do not
include zones that have delays (entry/exit zones, interior
w/delay) or 24-hour zones, as these zone types may produce
unpredictable operation and may not function as intended.
See field *85 for Cross Zone Timer option.
• Zone List 6:
V21iPSIA:
option.
• Zone List 7:
V21iPSIA:
option.
Menu Mode Programming
See field *50 for Dial Delay Disable
See field *93 for Unlimited Reports
5-13