Input Device Type (In)
10 INPUT TYPE
2 = AW (Aux wired zone)
RF TRANS
3
3 = RF (supervised RF transmitter)
4 = UR (unsupervised RF transmitter)
5 = Button type RF transmitter (unsupervised).
[ ∗ ] to continue
This prompt is skipped for zones 2-8, or 2-16 if zone-doubling was enabled at "Hardwire
Type" prompt.
All of the RF transmitters have one or more unique factory-assigned input (loop) ID codes.
Each of the inputs requires its own programming zone (e.g., a 5804's four inputs require
four programming zones).
RF Transmitters can be enrolled as one of the following types:
Type
RF
(Supervised RF)
UR
(Unsupervised RF)
BR
(Unsupervised
Button RF)
NOTE:
• For the built-in hardwired zones, the Input Device type is automatically displayed as HW
• To change the input type of a previously programmed wireless device (type RF, UR, BR)
Serial number Entry and Loop Number Entry
10 INPUT S/N:
L
[ ∗ ] to continue
A 0 2 2 - 4 0 6 4
1
Used only when enrolling wireless transmitters.
a. Transmit two open/close sequences. If using a button-type transmitter, press and
OR
b. Manually enter the 7-digit serial number printed on the label of the transmitter. Then
c. Press key [C] to copy the serial number previously enrolled (used when programming a
Loop Number Change
10 INPUT S/N
L
[ ∗ ] to continue
A 0 2 2 - 4 0 6 4
?
NOTE: If the [C] key is used to copy the previously enrolled serial number, the cursor will
move to the Loop column (L) with the previous serial number displayed, and display a
highlighted question mark for the loop number.
Enter the loop number and press [✱]. The system will now check for a duplicate serial/loop
number combination.
Enroll Summary
10 INPUT S/N
L
[ ∗ ] to continue
A 0 2 2 - 4 0 6 4
1
If the serial/loop number combination is not a duplicate in the system, a display showing
the serial number and loop number entry will appear.
Confirmation Option
XMIT TO CONFIRM
[ ∗ ] to continue
PRESS
TO SKIP
This prompt will only appear if you answered "Yes" at the first prompt in this section.
The system will enter a confirmation mode so that the operation of the actual programmed
input can be confirmed.
Activate the loop input or button that corresponds to this zone.
Description
Sends periodic check-in signals, as well as fault, restore, and low-
battery signals. The trans. must stay within receiver's range.
Sends all the signals that the "RF" type does, but the control does
not supervise the check-in signals. The transmitter may therefore be
carried off-premises.
Sends only fault signals. It will not send a low-battery signal until it
is activated. The transmitter may be carried off-premises.
and cannot be edited.
to a wired zone (type AW), you must first delete transmitter's serial number (see To
Delete A Serial Number prompt on next page)
release the button twice, but wait about 4 seconds before pressing the button the second
time.
press the [✱] key – the cursor will move to the "L" position. You can edit the loop
number, if necessary. When the loop number is acceptable, press [✱].
transmitter with several input loops).