• Can be used on a zone when an output relay action is desired, but with no accompanying
Type 23 *
No Alarm
alarm (e.g., lobby door access).
Response
• Usually assigned to all sensors or contacts on exterior doors and windows where bells and/or
Type 24
Silent Burglary
sirens are NOT desired.
• Provides an instant alarm, with NO audible indication at any keypad or external sounder, if
the zone is faulted when the system is armed in the Away, Stay, Instant, or Maximum modes.
• A report is sent to the central station.
• Assign to zone wired to a keyswitch.
Type 77
Keyswitch
• Do not use devices assigned as input type "BR" with this zone type.
• Assign to zone connected to AVS module.
Type 81
AAV Monitor
• Monitors 2-way voice sessions as follows:
Zone (for AVS)
- When the zone is faulted, all alarm sounding and dialer reporting stops, except
for fire alarms, which immediately terminate the voice session and cause
a fire report to be sent.
- When the zone is restored (session ended), sounding resumes (if bell timeout
has not expired) and reports that were stopped are sent.
Types 90-93
Allows for various custom responses. Options include response to entry/exit delays, response
Configurable
opens/shorts, types of alarm/trouble sounding, dial delay, and unique Contact ID report codes.
Types 92 and 93 can only be programmed via downloader. UL installations: Zone Types 90 -93
may not be used as fire or burglar alarm zones on fire or UL burglar alarm installations.
* The system can still be armed when these zone types are in a faulted condition.