SECTION 3
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION
This product incorporates field-programmable software. In order for the product to comply with the requirements in the
Standard for Control Units and Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be
limited to specific values or not used at all as indicated below:
Program feature
Permitted in
or option
UL 864? (Y/N)
Trouble Call Limit
Remote Download

3.1 User Programming

The MS-5UD/MS-10UD FACP is completely field programmable using the panel keypad and
requires no special software skills. While programming the FACP, the fire protection capabilities of
! ! !
the control panel are enabled. Programming Mode times-out after 10 minutes of inactivity.
Site-specific programming may be accomplished in the following ways:
Manual programming or editing, using the FACP keypad
Remote Programming and Editing Feature - allows creation and editing of site-specific
custom programs using a Windows-based computer and modem. For programs requiring a
large amount of data entry, this method may be preferred. A PK-CD programming CD ROM
can be ordered for this purpose
Local Programming and Editing Feature - allows creation and editing of site-specific custom
programs using a Windows-based computer and USB connection. For programs requiring a
large amount of data entry, this method may be preferred. A PK-CD programming CD ROM
can be ordered for this purpose
The System All Normal screen will be displayed in a programmed system with no active alarms,
troubles or supervisories, as illustrated below:
Read Status mode can be entered while the panel is in any mode of operation. If an alarm or
supervisory event exists at the panel, the event must be cleared before entering Programming mode.
To access any of the programming or read status features, the Enter or Mode key must be pressed,
which will cause the LCD to display the following:
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008

Programming

AND OTHER INVOLVED PARTIES
Refer to "Trouble Call Limit (Dialer Runaway Preven-
tion)" on page 99.
Trouble Call Limit = 0 (factory default): unlimited
N
calling to Central Station for any trouble condition
Trouble Call Limit = 1 - 99: limits call for each unique
trouble to from 1 to 99 within a 24 hour period
Refer to "Remote Download" on page 129.
Y
Remote Download - Proprietary No
Remote Download - Proprietary Yes
SYSTEM ALL NORMAL
10:00A 070707
1=READ STATUS MODE
2=PROGRAMMING MODE
3=FUTURE USE
4=REMOTE DOWNLOAD
Possible settings
Programming
Settings permitted
in UL 864
Trouble Call Limit =
0 for unlimited Cen-
tral Station trouble
calls
Remote Download
Proprietary Yes for
Proprietary system
intended to protect
only contiguous
properties
55