Programming
SYSTEM SETUP
1=TIMERS
2=BANNER
3=TIME-DATE
System Setup Screen #1
TIMERS
1=PAS DELAY
120
2=PRE SIGNAL
120
3=WATERFLW DELAY
0
Timer Screen #1
74
3.5.4.1 Timers
Timer delays for PAS, Pre-signal and waterflow activation can be programmed by pressing 1
while viewing System Setup Screen #1. The following screen will be displayed:
1=PAS DELAY
2=PRE SIGNAL
3=WATERFLW DELAY
1=AC LOSS DELAY
3.5.4.1.1 PAS (Positive Alarm Sequence) Delay
The factory default setting for PAS is 000 for no delay. To select a PAS delay of 001 to 180
seconds for all devices programmed for PAS, press 1 while viewing Timer Screen #1. The
following display will appear:
RANGE 000-180 SECONDS
A flashing cursor is positioned in the lower left corner of the display. Enter a delay time
consisting of three digits, such as 005 for five seconds. Upon entering the third digit, the time
delay will be stored in the control panel memory and the display will return to the Delay Screen
which will indicate the new delay time.
3.5.4.1.2 Pre-signal Delay
The factory default setting for Pre-signal delay is 000 for no delay. To select a Pre-signal delay
of 001 to 180 seconds for all devices programmed for Pre-signal, press 2 while viewing Timer
Screen #1. The following screen will be displayed:
PRESIGNAL DELAY
RANGE 000-180 SECONDS
TIMERS
Timer Screen #1
TIMERS
Timer Screen #2
PAS DELAY
PAS Delay Screen
Pre-signal Delay Screen
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
120
120
0
2