Programming
The following table lists the Zone Alarm Types that can be programmed for zones 1 through 10
and the corresponding Event Codes for Ademco Contact ID and SIA DCS Formats. Note that
Table 3.3 on page 93, Table 3.4 on page 94, Table 3.5 on page 95 and Table 3.6 on page 97 list
the default settings for Zone 1 through Zone 10. These can be changed to any of the Types
listed in Table 3.2 .
Note: The third character in the SIA-DCS Format (x in the table below) represents the zone
number.
Zone Alarm Type
Pull-Station
Waterflow
Waterflow Nonsilenceable
Combo
Combo AutoResettable Supervisory
2-Wire Detector
Normally Open Contact
Fire
Tamper
Supervisory
Supervisory AutoResettable
Medic-Alert
Hazard-Alert
Tornado-Alert
Proc-Mon
Procmon-AR
AC-Loss-Mon
Drill-Switch
Drill-Switch AutoResettable
The following tables list all of the Events and their default Event Codes for the Ademco Contact
ID and SIA-DCS Communication Formats.
Note: A detector freeze condition will be reported as a Supervisory Event Code.
92
Table 3.2 Zone Alarm Type Event Codes
Ademco Contact ID
Active
115
113
113
113
113
111
110
110
144
200
200
100
150
150
200
200
301
604
604
SIA-DCS Format
Active
Restoral
FAx
FHx
SAx
SHx
SAx
SHx
SAx
SHx
SAx
SHx
FAx
FHx
UAx
UHx
FAx
FHx
TAx
THx
FSx
FVx
FSx
FVx
MAx
MHx
PAx
PHx
PAx
PHx
IAx
IRx
IAx
IRx
ATx
ARx
FIx
FKx
FIx
FKx
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008