Operating Instructions
Fourth line in display:

4.6 Supervisory Operation

Supervisory operation is similar to alarm operation but with the following differences:
The piezo sounder pulses ½ second On and ½ second Off
The Supervisory LED flashes ½ second On and ½ second Off
The LCD displays the status label Active Supervisory along with the device name, type,
adjective/noun, associated zones and time/date
Communicate the supervisory condition to the Central Station
The supervisory relay is activated
The alarm relay is not activated
Silenced alarms are not resounded
Timers are not started
Store event in history buffer
Terminate upload or download communications
A typical Supervisory event would be displayed as illustrated in the following:
In the preceding example:
Note that, like alarms, supervisory signals latch, except when programmed for supervisory
autoresettable. Supervisory activations do not cause silenced alarms to resound, as do other alarm
conditions. Open circuits in supervisory wiring are processed by the control panel the same way as
other trouble conditions. Refer to "Alarm Operation" on page 111, for a description of the
information displayed on the control panel LCD.
112
Time; the current time in this example is 10:00A which represents 10:00 AM
Date; the current month, day and year in this example is 09 for September, 08 for the 8th
day of the month and 07 for the year 2007
FREEZE
<ADJ> <NOUN>
ZONE 05
10:00A 070707
FROZEN SUPRV - indicates zone detector is below approximately 45
SUPERVISORY
FROZEN SUPRV
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008