3.5.4 System Setup

System Setup allows the programmer to configure the following control panel features:
PROGRAMMING
1=SYSTEM SETUP
Pressing 1 for System Setup, while viewing Programming Screen #2, will cause the following
2=OPTION MODULES
screens to be displayed:
3=HISTORY
Programming Screen #2
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
Timers: This option allows the programmer to set the PAS (Positive Alarm Sequence) time
delay, Pre-Signal time delay and Waterflow time delay
Banner: This option allows the user to change the top two lines of the LCD display from the
factory default readout, which is blank, to a user defined readout when the control panel is in
Normal condition
Time-Date: This feature allows the programmer to set the time, display format (24 hr or 12
hr), date and daylight savings time feature into the FACP memory
Trouble Reminder: This feature, when enabled, provides an audible reminder that an alarm or
trouble still exists on the FACP after the control panel has been silenced. The control panel
piezo sounder will pulse once every 15 seconds during an alarm and every two minutes
during a trouble condition, after the Alarm Silence or Acknowledge key is pressed. The
piezo will continue to sound at these rates until the alarm or trouble condition is cleared. If
the Trouble Reminder feature is not enabled and a trouble condition is not cleared within 24
hours, the panel will reactivate the trouble sounder and retransmit the trouble condition to the
central station if connected
Canadian Option: This option allows the automatic programming of the FACP to Canadian
specifications (refer to "Canadian Option" on page 79).
Important! For Canadian Applications, this option must be set to ON prior to any other
panel programming.
Charger Disable: This option allows the programmer to disable the onboard battery charger
in the event an external battery charger is being used
1=TIMERS
2=BANNER
3=TIME-DATE
1=TROUBLE REMIND
2=CANADIAN OPTION OFF
3=CHARGR DISABLE
SYSTEM SETUP
System Setup Screen #1
SYSTEM SETUP
System Setup Screen #2
Programming
NO
NO