Honeywell MS-5UD Series Manual page 135

Hide thumbs Also See for MS-5UD Series:
Table of Contents

Advertisement

Table 7-3 contains three columns for calculating current draws. For each column, calculate the
current and enter the total (in amperes) in the bottom row. When finished, copy the totals from Cal-
culation Column 2 and Calculation Column 3 to Table 7-4 on page 136.
TABLE 7-3:System Current Draw Calculations
Calculation Column 1
Primary, Non-Fire Alarm Current
Device Type
(amps)
Qty
Main Circuit Board
MS-5UD
1
or
MS-10UD
CAC-5X
[
]
4XTMF
[
]
1 max.
ANN-80
[
]
ANN-I/O
[
]
ANN-RLY
[
]
2
[
]
ANN-(R)LED
ANN-S/PG
[
]
2-wire Detector
[
]
Heads
4-wire Detector
[
]
Heads
Power Supervision
[
]
4
Relays
5
NAC #1
NAC #2
NAC #3
NAC #4
Current Draw from
6
TB9 (nonalarm
)
Sum each
7
column
for
totals
Primary Non-Alarm =
Table Footnote
1. If using the Reverse Polarity Alarm output, add 0.005 amps; if using the Reverse Polarity Trouble output,
add another 0.005 amps.
2. ANN-LED is supplied standard with the MS-5UDC and MS-10UDC
3. Refer to the Device Compatibility Document for standby current.
4. Must use compatible listed Power Supervision Relay.
5. Current limitation of Terminal TB5 circuits is 2.5 amps per NAC for the MS-5UD-3(E), MS-10UD-3(E) and
3.0 amps per NAC for the MS-5UD-7(C/E), MS-10UD-7(C/E)
6. The total standby current must include both the resettable (TB9 Terminals 3 & 4) and nonresettable/
resettable (TB9 Terminals 1 & 2) power. Caution must be taken to ensure that current drawn from these
outputs during alarm does not exceed maximum ratings specified. Current limitations of TB9, Terminals 1 &
2 = 0.500 amps, filtered, 24 VDC +/-5%, 120 Hz ripple @ 10 mV
Terminals 3 & 4 = 0.500 amps, filtered, 24 VDC +/-5%, 120 Hz ripple @ 10mV
7. Total current draw listed above cannot exceed 3.0 amps for MS-5UD-3(E), MS-10UD-3(E) or, 7.0 amps for
MS-5UD-7(C/E), MS-10UD-7(C/E).
8. The current draw shown represents one zone (IDC) on the main circuit board in alarm. One zone consumes
0.040 amps
9. Enter the number of IDCs used minus one
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
Calculation Column 2
Secondary, Fire Alarm Current
(amps)
X[current draw]=
Total
Qty
X[0.080]=
1
X[0.085]=
X[0.001]=
[
X[0.005]=
[
1 max.
X[0.037]=
[
X[0.035]=
[
X[0.015]=
[
X[0.028]=
[
X[0.045]=
[
3
X[
]
=
[
3
X[
]
=
[
X[0.025]=
[
[
[
[
]=
Secondary Alarm =
X [current draw] =
Total
1, 8
X[0.235]
=
1, 8
X[0.265]
=
]
X[0.001]=
1
]
X[0.011]
=
]
X[0.040]=
]
X[0.200]=
]
X[0.075]=
]
X[0.068]=
]
X[0.045]=
9
X[0.040]=
]
9
X[0.040]=
]
]
X[0.025]=
]
X[
]=
]
X[
]=
[
]=
, nonresettable power and TB9,
RMS
Power Supply Calculations
Calculation Column 3
Secondary, Non-Fire Alarm Current
(amps)
Qty
X[current draw]=
Total
X[0.100]=
1
X[0.127]=
[
]
X[0.001]=
[
]
X[0.005]=
1 max.
[
]
X[0.015]=
[
]
X[0.035]=
[
]
X[0.015]=
[
]
X[0.028]=
[
]
X[0.045]=
3
[
]
X[
]
=
3
[
]
X[
]
=
[
]
X[0.025]=
[
]=
Secondary Non-Alarm =
, resettable power.
RMS
135

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ms-10ud series

Table of Contents