INPUT ZONE #
1=FREEZE SUPV.
NO
2=ACC MSG #
Edit Input Zone Screen #4
INPUT ZONE #
1=NOUN/ADJECTIVE
2=DESCRIPTION
*****************
Edit Input Zone Screen #5
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
ACC Message
Pressing 2 for ACC MSG # while viewing Edit Input Zone Screen #4 will cause the following
screens to be displayed:
ACC MSG NUMBER
1=NO MSG-ACTIVE
2=NO MSG-INACTIVE
3=MESSAGE 1
ACC MSG NUMBER
1=MESSAGE 2
2=MESSAGE 3
3=MESSAGE 4
ACC MSG NUMBER
1=MESSAGE 5
Using these screens, the programmer can assign an audio message to each input zone. The NO
MSG-ACTIVE option is the factory default selection which means that no message has been
programmed for the input zone but its corresponding ACC-25/50ZS audio zone will turn on
when this input zone goes active (if an input zone with a programmed audio message goes
active, the message will also be played over this zone). The NO MSG-INACTIVE option will
not turn on the corresponding ACC-25/50ZS audio zone when this input goes active. If
MESSAGE 1 through 5 is the programmed option, the selected message will play when the
FACP is connected to an ACC-25/50ZS Audio Panel via the ANN-BUS and the corresponding
FACP input zone goes into alarm.
Noun/Adjective
The Noun/Adjective selection allows the programmer to enter specific descriptors about the
detector currently being programmed. Pressing 1 while viewing Edit Input Zone Screen #4 will
cause the following screen to be displayed:
1=STANDARD ADJECTIVE
2=STANDARD NOUN
3=CUSTOM ADJECTIVE
4=CUSTOM NOUN
ACC Message Screen #1
ACC Message Screen #2
ACC Message Screen #3
Noun/Adjective Screen
Programming
63