APPENDIX C
Keltron 95M3158 TTM-RPS
1. Terminals 7 and 8: Remote station alarm/trouble inputs.
2. Terminals 9 and 10: Sprinkler supervisory input.
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008

FACP with Keltron

The following figure illustrates the connections between the FACP and Keltron
Receiver/Transmitter.
CAUTION! For reasons of wiring diagram clarity, terminal designations of Keltron
modules are not shown in actual order. Follow Keltron manual and module markings
for exact terminal locations to prevent severe module damage!
IMPORTANT! All connections between the FACP and Keltron modules must be made
within 20 feet and enclosed within conduit or equivalently protected against mechanical
injury.
Sprinkler Supervisory Signal
Note: Cut TBL jumper on 4XTMF module to send
alarm/trouble signal from the same pair or terminals.
Fire Alarm Control Panel
(terminal blocks are not shown in
their actual positions in order to
clarify wiring connections)
Figure C.1 Keltron Wiring
Alarm/Trouble Signal
4XTMF Module
FACP with Keltron
*Note: For more information,
refer to Keltron manual.
149