NFPA 72 Auxiliary Fire Alarm System
All connections are power-limited and supervised. This application is not suitable for separate
transmission of sprinkler supervisory or trouble conditions.
Notes:
1. 3 ohms maximum loop resistance allowed for wiring from control panel to Municipal Box.
2. Cut JP30 on the MS-5UD/MS-10UD main circuit board to supervise placement of 4XTMF
module and circuit.
3. Cut JP24 on the MS-5UD/MS-10UD main circuit board to enable FACP Supervisory relay.
4. Refer to "4XTMF Transmitter Module Installation" on page 37 for detailed information.
Polarities shown in alarm condition
Figure B.2 Municipal Box Connected to 4XTMF Transmitter Module
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
NFPA Standard-Specific Requirements
Municipal Box
Circuit
Nonpower-limited
-
+
4XTMF
FIRE
+
-
Gamewell Model M34-
56 Local Energy
Municipal Box
145