4: Dry Contact Wiring - Honeywell Farenhyt IFP-75HV Manual

Addressable fire alarm control panel
Hide thumbs Also See for Farenhyt IFP-75HV:
Table of Contents

Advertisement

5880 LED Driver Module
LED1
LED2
LED3
LED4
LED5
LED6
LED7
LED8
LED9
LED10
LED Power
no connection
LED11
LED12
LED13
LED14
LED15
LED16
LED17
LED18
LED19
LED20
LED Power
no connection
4.11.4 Dry Contact Wiring
The eight input circuits on the 5880 board are for monitoring switch inputs. Any type of switch supported by the control panel can be used
with the 5880. For example, you can use a 5880 to monitor pull stations, water flow, tamper, reset, or silence switches.
Wire dry contacts as shown below. Notice grouping of terminals. Power terminals are shared by two inputs.
4.7kΩ EOL
IFP-75 Series Manual — P/N LS10147-001SK-E:E 4/6/2022
P1
Pin #
1
2
3
4
5
6
7
8
9
10
11
12
P2
Pin #
1
2
3
4
5
6
7
8
9
10
11
12
Figure 4.32 5880 Board Layout
resistors
IN - 48
C+
IN - 47 IN - 46
5880
Figure 4.33 Dry Contact Wiring
C+
IN - 45 IN - 44
C+ IN - 43 IN - 42
Control Panel Installation
Cathode
LEDs
Anode
Cathode
P3 and P4 are wired
LEDs
the same as P2.
Anode
supervised
wiring
C+
IN - 41
45

Advertisement

Table of Contents
loading

This manual is also suitable for:

Farenhyt ifp-75

Table of Contents