Control Panel Installation
RA-1000/R installation involves the following steps:
1.
Ensure the power is off at the panel.
2.
Mount the RA-1000/R in the desired location (see Section 4.8.1).
3.
Connect the RA-1000/R to the panel (see Figure 4.11).
4.
Use the DIP switches on the back of the RA-1000 to assign an ID# to the annunciator (see Section 4.13.1).
5.
The new RA-1000/R module must be added to the system through programming. JumpStart will add the module automatically
(see Section 8.1). You can also add it manually (see Section 8.2.2). Select a name, if desired.
4.8.1 Mounting the RA-1000/R
This section of the manual describes mounting the remote annunciator. The annunciator can be flush- or surface-mounted. Figure 4.19 shows
the parts of the annunciator. Instructions for disassembling and mounting appear on the following pages.
The RA-1000/R comes from the factory fully assembled. You must disassemble it for mounting. To disassemble the annunciator, use a 5/64
hex wrench to remove the set screws, located on the bottom of the annunciator bezel. (See Figure 4.20 for location of the set screws.)
Flush Mounting
This section of the manual describes flush mounting. You can flush-mount with or without an electrical box.
Flush Mounting with an Electrical Box
The RA-1000/R annunciator can be used with the following types of electrical boxes: 4S, single-gang, and double-gang.
38
Figure 4.19 Annunciator Parts
surface mounting holes
holes for inserting wires
for flush-mounting
(located in all corners)
Set Screw
Figure 4.20 Annunciator Backbox and Bezel Details
RA-1000 Remote Annunciator Installation
FIRE ALARM ANNUNCIATOR
knockouts
knockouts
IFP-75 Series Manual — P/N LS10147-001SK-E:E 4/6/2022
screws for placement
of mounting wires