3: Current Draw Worksheet For Sk Slc Devices - Honeywell Farenhyt IFP-75HV Manual

Addressable fire alarm control panel
Hide thumbs Also See for Farenhyt IFP-75HV:
Table of Contents

Advertisement

Calculating Current Draw and Standby Battery
Wireless Modules
WIDP-WGI Wireless Gateway
A
Total System Current
Auxiliary Devices
IPDACT-2 IP Communicator
IPDACT-2UD IP Communicator
CELL-MOD/CELL-CAB-SK
HWF2-COM Series
B
Auxiliary Devices Current
Notification Devices
5495/5499 Power Supply
C
Notification Appliances Current
D
Total current ratings of all devices in system (line A + line B + C)
E
Total current ratings converted to amperes (line D x 0.001):
F
Number of standby hours
G
Multiply lines E and F.
H
Alarm sounding period in hours. (For example, 5 minutes = 0.0833 hours)
I
Multiply lines E and H.
J
Add lines G and I.
Multiply by the Derating Factor
Total ampere hours required
1
The FACP can only support 5 devices with LEDs on. The current draw has been added to the panels alarm current.
2
Total does not include isolator devices or accessory bases.
3
The IDP-BEAM-T draws a maximum of 500mA from auxiliary power when the test feature is used. This should be considered when
determining auxiliary power capacity but not calculated into current requirements for everyday operation.
4
The IDP-PHOTO-R/-W/-IV is sold separately from the DNR. Current draw for the DNR + IDP-PHOTO-R/-W/-IV is calculated by increasing
the "Number of Devices" column for each IDP-PHOTO-R/-W/-IV used with a DNR.
5
Maximum SBUS address capacity is determined by the amount of SBUS bandwidth consumed by each SBUS module. Refer to
Section 4.6.2 for SBUS limitations.
6
If there are door holders in the system, there is no need to consider door holder current for alarm/battery standby, because power is
removed during that time. However, during normal operation, door holders draw current and must be included in the 1.8 A total current that
can be drawn from the panel.
7
Use next size battery with capacity greater than required.
3.5.3 Current Draw Worksheet for SK SLC Devices
Use Table 3.3 to determine the current requirements during the alarm/battery standby operation when SK SLC devices are installed. You can
install up to 75 SK detectors and 75 SK modules
For each device, use this formula:
IFP-75 Series Manual — P/N LS10147-001SK-E:E 4/6/2022
Device
# of Devices
Refer to devices manual for current rating
6
Refer to device manual for current rating
7
Table 3.2 Current Draw Worksheet for IDP SLC Devices (Continued)
1
.
Device
# of Devices
This column
Table 3.3 Current Draw Worksheet for SK SLC Devices
Current per Device
Max current using ext supply
Max current SLC Power
Standby:
Alarm:
Standby:
Alarm:
Standby:
Alarm:
Standby:
Alarm:
Alarm/Standby:
Alarm/Standby:
Standby:
Alarm:
Alarm:
Alarm:
Alarm:
Total standby AH
Total alarm AH
Current per Device
X
This column
Prerequisites for Installation
Standby
Alarm Current
Current
40 mA
mA
24 mA
mA
93 mA
mA
136 mA
98 mA
mA
155 mA
55 mA
mA
100 mA
210 mA
mA
290 mA
mA
mA
mA
mA
75 mA
205 mA
mA
mA
mA
mA
A
H
AH
AH
1.25
AH
Standby
Alarm Current
Current
=
Current per number of devices.
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
A
H
AH
19

Advertisement

Table of Contents
loading

This manual is also suitable for:

Farenhyt ifp-75

Table of Contents