5: Miscellaneous Options; 6: Daylight Saving Options - Honeywell Farenhyt IFP-75HV Manual

Addressable fire alarm control panel
Hide thumbs Also See for Farenhyt IFP-75HV:
Table of Contents

Advertisement

System Options
Auto-Resound (4 or 24 hours)
The system resound time period can be modified from the default value 24 hours to 4 hours. This setting adjusts when the FACP will auto-
matically resound events after being silenced. Set this option to 4 hours when using SWIFT devices.
8.6.5 Miscellaneous Options
Through this programming option, you can turn on or off strobe synchronization during silence, display status at Idle (auto display event),
report by zone or point, and single key acknowledge.
To edit miscellaneous options:
1.
Login to the panel.
2.
Select 7 to access the program menu.
3.
Select 5 to access System Options.
4.
Select 5 to access Miscellaneous Options.
Strobes Active when Silenced
When "SYNC Strobe" is selected as Y (Yes), the strobes will continue to flash when the system is silenced and will stop flashing when the
system is reset.
NOTE: "SYNC Strobe" only functions with outputs that use a synchronized output pattern.
5.
Press the up or down arrow key to toggle this selection between Y (Yes) or N (No).
6.
Press right arrow key or ENTER to make your selection and move to the next programming option.
Auto Display Events
When this feature is programmed Y (Yes), the highest priority event of the system in control will automatically display on the control panel
and remote annunciators after there has been no activity on any system touch pad for two minutes.
7.
Press the up or down arrow key to toggle this selection between Y (Yes) or N (No).
8.
Press right arrow key or ENTER to make your selection and move to the next programming option.
8.6.6 Daylight Saving Options
To edit daylight savings:
1.
Login to the panel.
2.
Select 7 to access the program menu.
3.
Select 5 to access System Options.
4.
Select 6 for Daylight Savings.
Automatic Daylight Saving Adjustment
The control panel has an automatic DST (Daylight Saving Time) adjustment feature. If this feature is not enabled (set to No), the Daylight
Saving Time change is not made to the system clock.
To enable or disable DST adjustment, continue programming:
5.
Select Y (enabled) or N (disabled) by pressing the up or down arrow, then press ENTER.
Daylight Saving Time Start and End
This option allows you to adjust the week and month Daylight Saving Time (DST) starts and ends. For this feature to work, you must enable
(set to Yes) the Automatic Daylight Savings Adjustment option under Daylight Savings Options. The default values for the DST Start and
End are:
DST Start: The second Sunday in March
DST End: The first Sunday in November
To set the start and end for Daylight Saving Time, refer the following steps:
1.
Press the up or down arrow key to select the week (1st, 2nd, etc.) Daylight Saving Time starts.
Then, press ENTER to make your selection and move the cursor to the month setting.
2.
Press the up or down arrow key to select the month (January – December) Daylight Saving Time starts.
Then, press ENTER to make your selection and move the cursor to the DST End option.
3.
Press the up or down arrow key to select the week (1st, 2nd, etc.) Daylight Saving Time ends.
Then, press ENTER to make your selection and move the cursor to the month setting.
4.
Press the up or down arrow key to select the month (January – December) Daylight Saving Time ends.
Then, press ENTER two times to make your selection and exit.
IFP-75 Series Manual — P/N LS10147-001SK-E:E 4/6/2022