Programming
low AC report delay
clock format
enable or disable automatic daylight savings time adjustment
AC clock frequency
Waterflow Delay
You can program a delay of 0-90 seconds (zero means no delay) to be used in conjunction with a waterflow switch. The delay is system-
wide. All waterflow switches on the system will use the same delay period.
To access the screen for programming water flow delay, follow these steps:
1.
Login to the panel.
2.
Select 7 to access the program menu.
3.
Select 5 to access System Options.
4.
Select 4 to access Time Options.
A screen similar to the one shown below will display.
Water Flow Delay:01s
Alarm Verify:060s
AC Report Delay:03h
<(0-90)>
5.
Enter the number of seconds (0 to 90) to delay an a waterflow switch alarm, then press ENTER.
Alarm Verify
You can set the alarm verification time from 60 to 250 seconds (default is 60 seconds).
NOTE: For UL installations, the Alarm Verification Time cannot be less than 60 seconds.
To set the alarm verification:
6.
Enter the desired number of seconds for the alarm verification time.
7.
Press the right arrow or press ENTER to make your selection and move the cursor to the next programming option.
AC Report Delay
NOTE: You must select 1-3 hours in UL central station installations and UL remote signaling installations.
You can adjust the number of hours before a low AC report will be sent to the central station.
To program a low AC report delay, follow these steps:.
8.
Enter the number of hours before a low AC report will be sent to the central station, then press ENTER.
AC Line Frequency
The panel's AC line frequency is selectable for 50 or 60 Hz or Internal. The AC Frequency feature dictates how the control panel will calcu-
late time based on the AC line frequency used in the installation site. The "Internal" option can be used in areas where the AC line frequency
is not dependable and you want the panel to calculate time from the internal crystal. The internal crystal is not as accurate as the AC power
source and internal 60 Hz or 50 Hz should normally be selected. The panel defaults to the 60 Hz selection. To change the AC line frequency,
continue programming from steps above:
9.
Select 50 Hz, 60 Hz or Intl, by pressing the up or down arrow key. Then, press ENTER.
Clock Display Format (AM/PM or Military)
To change the system clock display format, continue programming from step 8 above:
10. Select AMPM (for AM/PM display format) or MIL (for military or 24 hr display format) by pressing the up or down arrow, then press
ENTER.
92
delay in seconds
before waterflow
alarm occurs (00-90)
More
Figure 8.14 Water Flow Delay Programming Screen
Water Flow Delay:01s
Alarm Verify:060s
AC Report Delay:03h
<Low AC(0-30h)> More
Figure 8.15 Low AC Report Delay Programming Screen
AC-Frequency: 60Hz
Clock Format: AMPM
Auto-Resound: 24hr
<50Hz/60Hz/Internal>
low AC report delay
in hours (00-30)
IFP-75 Series Manual — P/N LS10147-001SK-E:E 4/6/2022