Sia / Ifp-75 Panels Pi Modifier Reporting - Honeywell Farenhyt IFP-75HV Manual

Addressable fire alarm control panel
Hide thumbs Also See for Farenhyt IFP-75HV:
Table of Contents

Advertisement

Reporting

10.2 SIA / IFP-75 Panels PI Modifier Reporting

Events are sent to the Central Station as a variable length string:
The Event Format is:
EEZZZZ
Where the Event Format is defined as follows:
Code
Event Code Description
Event Code (2 characters)
EE
ZZZZ
Event parameter (up to four digits – not zero filled)
The account number is sent using an account block that is separate from the event block.
Multiple events can be sent within a single event block. Events are separated by a "/" character.
The event parameter can be a zone, point or module number.
When reporting-by-point is enabled, the communicator uses a "pi" event to supersede the actual point event to report the module to
which the point is linked.
The panel ID is not sent in the SIA event parameters.
See Table 10.3 below for an example.
Event
Fire Alarm-Zone
Fire Alarm-Zone
Fire Alarm-Point
Fire Alarm-Point
Expander Trouble
Auto Test
Battery Trouble-Panel 32
Battery Trouble-Expander 18
SLC Loop Shorted
Program Begin Panel ID=32
Program Begin Panel ID= 22
AC Power Loss - Panel 22
Fire Trouble
Fire Trouble
Fire Trouble-NAC
Fire Trouble-NAC
118
Report
Panel
Module
Zone/Point
ID
Zone
n/a
n/a
Zone
n/a
n/a
Point
n/a
01
Point
n/a
33
n/a
n/a
11
n/a
n/a
n/a
n/a
n/a
98
n/a
n/a
18
n/a
n/a
44
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
98
Point
n/a
97
Zone
n/a
97
Point
n/a
98
Zone
n/a
98
Table 10.3 SIA- IFP-75 Panels - PI Modifier Reporting Examples
SIA / IFP-75 Panels PI Modifier Reporting
Zone
Point ZZZZ
ZZZZ
15
n/a
05
n/a
n/a
123
n/a
203
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
200
01
n/a
n/a
NAC Circuit 2
n/a
NAC Circuit 2
IFP-75 Series Manual — P/N LS10147-001SK-E:E 4/6/2022
Fields Sent
SIA Event Data
EE-ZZ
FA15
EE-Z
FA5
EE-ZZ /EE-ZZZ
pi01/FA123
EE-ZZ/EE-ZZZ
pi11/FA203
EE-ZZ
ET11
EE-Z
RP0
EE-ZZ
YT98
EE-ZZ
YT18
EE-ZZ
ET44
EE-Z
LB0
EE-Z
LB0
EE-Z
AT0
EE-ZZ /EE-ZZZ
pi97/FT200
EE-Z
FT1
EE-ZZ /EE-Z
pi98/FT2Z=Pt. #
EE-ZZZ
FT98 ZZZ=OP