Reporting
10.2 SIA / IFP-75 Panels PI Modifier Reporting
Events are sent to the Central Station as a variable length string:
The Event Format is:
EEZZZZ
Where the Event Format is defined as follows:
Code
Event Code Description
Event Code (2 characters)
EE
ZZZZ
Event parameter (up to four digits – not zero filled)
•
The account number is sent using an account block that is separate from the event block.
•
Multiple events can be sent within a single event block. Events are separated by a "/" character.
•
The event parameter can be a zone, point or module number.
•
When reporting-by-point is enabled, the communicator uses a "pi" event to supersede the actual point event to report the module to
which the point is linked.
•
The panel ID is not sent in the SIA event parameters.
See Table 10.3 below for an example.
Event
Fire Alarm-Zone
Fire Alarm-Zone
Fire Alarm-Point
Fire Alarm-Point
Expander Trouble
Auto Test
Battery Trouble-Panel 32
Battery Trouble-Expander 18
SLC Loop Shorted
Program Begin Panel ID=32
Program Begin Panel ID= 22
AC Power Loss - Panel 22
Fire Trouble
Fire Trouble
Fire Trouble-NAC
Fire Trouble-NAC
118
Report
Panel
Module
Zone/Point
ID
Zone
n/a
n/a
Zone
n/a
n/a
Point
n/a
01
Point
n/a
33
n/a
n/a
11
n/a
n/a
n/a
n/a
n/a
98
n/a
n/a
18
n/a
n/a
44
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
98
Point
n/a
97
Zone
n/a
97
Point
n/a
98
Zone
n/a
98
Table 10.3 SIA- IFP-75 Panels - PI Modifier Reporting Examples
SIA / IFP-75 Panels PI Modifier Reporting
Zone
Point ZZZZ
ZZZZ
15
n/a
05
n/a
n/a
123
n/a
203
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
200
01
n/a
n/a
NAC Circuit 2
n/a
NAC Circuit 2
IFP-75 Series Manual — P/N LS10147-001SK-E:E 4/6/2022
Fields Sent
SIA Event Data
EE-ZZ
FA15
EE-Z
FA5
EE-ZZ /EE-ZZZ
pi01/FA123
EE-ZZ/EE-ZZZ
pi11/FA203
EE-ZZ
ET11
EE-Z
RP0
EE-ZZ
YT98
EE-ZZ
YT18
EE-ZZ
ET44
EE-Z
LB0
EE-Z
LB0
EE-Z
AT0
EE-ZZ /EE-ZZZ
pi97/FT200
EE-Z
FT1
EE-ZZ /EE-Z
pi98/FT2Z=Pt. #
EE-ZZZ
FT98 ZZZ=OP