Ann-Bus Modules; Auto-Configure - Honeywell fire-lite alarms MRP-2002E Manual

Agent release control system
Hide thumbs Also See for fire-lite alarms MRP-2002E:
Table of Contents

Advertisement

Master Programming Level

3.5.7.2 ANN-BUS Modules

If an ANN-BUS module is installed, press 2 while viewing ANN-BUS screen #1 to select
ANN-BUS addresses for the module(s). The following screen will be displayed.
Pressing the down arrow key will allow the programmer to view additional screens displaying
Addresses 1 - 8. Pressing the number corresponding to the desired address will display a screen
with technical information about the selected module.
In the technical information screen, pressing 1 for Type will display the following screens:
Press the number corresponding to the module type, if any, that is installed with the selected
address. This will enable the module.

3.5.7.3 Auto-Configure

The ANN-BUS Auto-Configure features allows the programmer to quickly bring all installed
ANN-BUS modules online. The software will search for all ANN-BUS modules and
automatically program the device type and address into the system. Pressing 3 while viewing
ANN-BUS Screen #1 will begin the Auto-Configure process and cause the following screen to
be displayed:
MRP-2002 & MRP-2002E PN 53049:A1 5/01/2008
ANN-BUS MODULES
1=ADDR. 1
2=ADDR. 2
3=ADDR. 3
On Board DACT Screen #1
ANN-BUS MODULE TYPE
1=NONE
2=ANN-80
3=ANN-I/O
Module Type Screen #1
ANN-BUS MODULE TYPE
1=ANN-S/PG
2=ANN-RLY
3=ANN-LED
Module Type Screen #2
ANN-BUS
AUTO-CONGFIGURE
IN PROGRESS
PLEASE WAIT
Auto-Configure Screen
NONE
NONE
NONE
Programming