Discharge Timer - Honeywell fire-lite alarms MRP-2002E Manual

Agent release control system
Hide thumbs Also See for fire-lite alarms MRP-2002E:
Table of Contents

Advertisement

Master Programming Level

3.5.6.2.2 Discharge Timer

The Discharge Timer determines how long an agent release will continue once activated. The
factory default setting for the Discharge Timer is Always On. To program the Discharge Timer,
press 2 while viewing the Timer Screen #1. The following display will appear:
Pressing 1 while viewing the Discharge Setup screen will program the releasing circuit to
continue an agent release until the panel is reset.
Pressing 2 while viewing the Discharge Setup screen will cause the following screen to be
displayed:
A Discharge Time of 01 to 20 minutes can be programmed. A flashing cursor is positioned in
the lower left corner of the display. Enter a Discharge time consisting of two digits, such as 05
for five minutes. Upon entering the second digit, the time will be stored in the control panel
memory and the display will return to the Delay Screen which will indicate the new Discharge
time. In this example, when the corresponding agent releasing circuit is activated, it will
continue an agent release for five minutes after activation.
Note that if a Manual Release is activated, the Discharge Timer will be activated and the
release will continue for the duration of the Discharge Timer.
MRP-2002 & MRP-2002E PN 53049:A1 5/01/2008
DISCHARGE
1=ALWAYS ON
2=ENTER MINUTES
Discharge Setup Screen
DISCHARGE
RANGE 01-20 MINUTES
Pre-Discharge Setup Screen
Programming
67