Programming

3.5.7 ANN-BUS

PROGRAMMING
1=ANN-BUS
Optional ANN-BUS devices available for the FACP include annunciators, relay modules and
2=HISTORY
printer connection for acquiring hardcopy printouts of panel data. Pressing 1 while viewing
3=WALKTEST
Programming Screen #3 will cause the control panel to display the following screens.
Programming Screen #3
72

3.5.6.6 Charger Disable

Pressing 3 while viewing System Setup Screen #2 will allow the programmer to enable or
disable the onboard battery charger. If an external battery charger is being used, the onboard
battery charger must be disabled. Each press of the 3 key will toggle between Chargr Disable
No and Chargr Disable Yes.
1=BUS ENABLED
2=BUS MODULES
3=AUTO CONFIGURE
1=ANN-S/PG OPTIONS
2=ANN-I/O OPTIONS
3=ANN-80 OPTIONS
1=ANN-RLY OPTIONS
2=ANN-LED OPTIONS
An ANN-S/PG Printer module, ANN-I/O module, ANN-80 LCD annunciator module, ANN-
RLY relay module and ANN-LED module can be programmed into the FACP. These devices
communicate with the FACP over the ANN-BUS terminals on the control panel.

3.5.7.1 ANN-BUS Enabled

The ANN-BUS must be enabled if any modules are installed on the ANN-BUS terminals. To
enable the ANN-BUS, press 1 while viewing ANN-BUS screen #1 so that the display reads
ANN-BUS Enabled Yes. Each press of the 1 key will cause the display to toggle between ANN-
BUS Enabled Yes and ANN-BUS Enabled No.
ANN-BUS
ANN-BUS Screen #1
ANN-BUS
ANN-BUS Screen #2
ANN-BUS
ANN-BUS Screen #3
MRP-2002 & MRP-2002E PN 53049:A1 5/01/2008