Maintenance Programming Level
Pressing 1 while viewing the History screen will cause the following screen to be displayed:
To view all the events which have occurred in the control panel since the history file was last
erased, press 1 while viewing the Events screen. To view only alarms which have occurred, press 2
while viewing the Events screen. To view events other than alarms, press 3. The most recent event
will be displayed on the screen. To view all of the selected events, press the up or down arrow keys
to scroll through the list of events. If no events have occurred, the display will read NO EVENTS
IN HISTORY.
Pressing 2 while viewing the History Screen will cause the following screen to be displayed:
Pressing 1 while viewing the Erase History Screen will erase all events from the History file. The
display will then return to the History Screen. Pressing 2 will cause the display to return to the
History Screen without erasing the History file.

3.6.3 Walktest

PROGRAMMING
To perform a walktest, press 3 while viewing Maintenance Screen #1. The following screen will be
1=INPUT ZONES
displayed:
2=HISTORY
3=WALKTEST
Maintenance Screen #1
The operator can press 1 to perform a silent walktest or 2 to perform an audible walktest. The
display will read UNIT IN WALKTEST. To end the Walktest, press the Esc (Escape) key.
Pressing 3 after the walktest has been completed, will allow the operator to view the results of the
walktest.
MRP-2002 & MRP-2002E PN 53049:A1 5/01/2008
HISTORY
1=VIEW ALL
2=VIEW ALARMS
3=VIEW OTHER EVENTS
ERASE HISTORY
PROCEED ?
1=YES
Erase History Screen
WALKTEST
1=SILENT
2=AUDIBLE
3=VIEW EVENTS
Walktest Screen
Programming
2=NO
83